The RFC screw unit is a refrigeration unit that integrates high efficiency, reliability, and energy saving, designed specifically for various industrial and commercial refrigeration needs. The unit features a compact overall structure and a highly integrated design, making installation easier and saving machine room space, while also facilitating maintenance and repair. RFC screw units cover a range of high, medium, and low temperature series, applicable to a wide range of storage temperatures, meeting refrigeration needs from evaporation temperatures of 10℃ to -40℃ or even lower, flexibly adapting to refrigeration system requirements under different operating conditions.
The core component of the unit uses semi-hermetic screw compressors from well-known domestic and international brands. These compressors offer advantages such as high efficiency and energy saving, long lifespan, low vibration, stable operation, and low noise, providing a solid guarantee for the reliable operation of the unit. RFC screw units also emphasize quality in their refrigeration system components. Key components such as oil separators, oil coolers, liquid receivers, economizers, pressure controllers, and electrical control boxes are all selected from well-known domestic and international brands, ensuring the high reliability and stability of the entire system.
The rack features a modular design, incorporating safety protection components such as shut-off valves, check valves, and safety valves to ensure both system safety and flexibility. This design not only facilitates transportation and installation but also allows for subsequent expansion or adjustments to the unit configuration, meeting the personalized needs of different users.
Equipment Parameters Introduction
Detail Display
Contact Us
Equipment Parameters Introduction
| Unit Model | Cam.Model (RFC) |
Com, Cuartity |
Condensing temp.(℃) |
Evaporation Temp.(℃) | Reservoi (L) |
Supply (mim) |
Suction (mm) |
Gas Outlet (Pm) |
liquid inletpipe (mm) |
Dimension(mm) (LxW×H) |
|||||||||
| -20 | -25 | -30 | -35 | -40 | |||||||||||||||
| Cooling Capacity/Power Input (kW) | |||||||||||||||||||
| LXPL-RFCF-30L | SLD120 -30 (30HP) |
1 | 35 | 58.7 | 19.8 | 48.8 | 19.1 | 40.1 | 18.4 | 32.5 | 17.9 | 25.8 | 15.6 | 80 | Ф28 | Ф57 | Ф45 | Ф35 | 1800×1400×1500 |
| 40 | 55.9 | 24 | 46.3 | 22.8 | 37 | 21.5 | 29.7 | 20.9 | 23 | 20 | |||||||||
| 45 | 53.4 | 26.2 | 43.4 | 25.8 | 35.3 | 24.8 | 26.9 | 24.3 | 20.3 | 23.5 | |||||||||
| LXPL-BRFCF2 -60L |
2 | 35 | 117.4 | 39.6 | 97.6 | 38.2 | 80.2 | 368 | 65 | 35.8 | 51.6 | 35.2 | 150 | Ф35 | Ф76 | Ф57 | Ф45 | 2400×1650×1700 | |
| 40 | 111.8 | 48 | 92.6 | 45.6 | 74 | 43 | 59.4 | 41.8 | 46 | 40 | |||||||||
| 45 | 106.8 | 52.4 | 86.8 | 51.6 | 70.6 | 49.6 | 53.8 | 48.6 | 40.8 | 47 | |||||||||
| LXPL-BRFCF3 -90L |
3 | 35 | 176.1 | 59.4 | 146.4 | 57.3 | 120.3 | 55.2 | 97.5 | 53.7 | 77.4 | 52.8 | 200 | Ф45 | Ф89 | Ф76 | Ф57 | 3000×1800×1700 | |
| 40 | 167.7 | 72 | 138.9 | 68.4 | 111 | 64.5 | 89.1 | 62.7 | 69 | 60 | |||||||||
| 45 | 160.2 | 78.6 | 130.2 | 77.4 | 105.9 | 74.4 | 80.7 | 72.9 | 61.2 | 70.5 | |||||||||
| LXPL-BRFCF4 -120L |
4 | 35 | 234.8 | 79.2 | 195.2 | 76.4 | 160.4 | 73.6 | 133 | 71.6 | 103.2 | 70.4 | 250 | Ф57 | Ф108 | Ф89 | Ф76 | 4500×2000×1800 | |
| 40 | 223.6 | 96 | 185.2 | 91.2 | 148 | 86 | 118.8 | 83.6 | 92 | 80 | |||||||||
| 45 | 213.6 | 104.8 | 173.6 | 103.2 | 1412 | 99.2 | 107.6 | 97.2 | 81.6 | 94 | |||||||||
| LXPL-RFCF-40L | SLD140 -40 (40HP) |
1 | 35 | 67.1 | 22.7 | 55.8 | 21.8 | 45.9 | 21.1 | 37.1 | 20.5 | 29.5 | 20.1 | 100 | Ф28 | Ф57 | Ф45 | Ф35 | 1800×1400×1500 |
| 40 | 64 | 27.5 | 53 | 26.1 | 42.3 | 24.6 | 34 | 23.9 | 26.3 | 22.9 | |||||||||
| 45 | 61.1 | 30 | 49.6 | 29.6 | 40.4 | 28.4 | 30.8 | 27.9 | 23.4 | 26.9 | |||||||||
| LXPL-BRFCF2 -80L |
2 | 35 | 134.2 | 45.4 | 111.6 | 43.6 | 91.8 | 42.2 | 74.2 | 41 | 59 | 40.2 | 200 | Ф35 | Ф76 | Ф76 | Ф57 | 2400×1650×1700 | |
| 40 | 128 | 55 | 106 | 52.2 | 84.6 | 49.2 | 68 | 47.8 | 56.2 | 45.8 | |||||||||
| 45 | 122.2 | 60 | 99.2 | 59.2 | 80.8 | 56.8 | 61.6 | 55.8 | 46.8 | 53.8 | |||||||||
| LXPL-BRFCF3 -120L |
3 | 35 | 201.3 | 68.1 | 167.4 | 65.4 | 137.7 | 63.3 | 111.3 | 61.5 | 88.5 | 60.3 | 250 | Ф45 | Ф89 | Ф76 | Ф57 | 3000×1800×1700 | |
| 40 | 192 | 82.5 | 159 | 78.3 | 126.9 | 73.8 | 102 | 71.7 | 78.9 | 68.7 | |||||||||
| 45 | 183.3 | 90 | 148.8 | 88.8 | 121.2 | 85.2 | 92.4 | 83.7 | 70.2 | 80.7 | |||||||||
| LXPL-BRFCF4 -160L |
4 | 35 | 256 | 110 | 212 | 104.4 | 169.2 | 98.4 | 136 | 95.6 | 105.2 | 91.6 | 300 | Ф57 | Ф108 | Ф89 | Ф76 | 4500×2000×1800 | |
| 40 | 201.3 | 68.1 | 167.4 | 65.4 | 137.7 | 63.3 | 111.3 | 61.5 | 88.5 | 60.3 | |||||||||
| 45 | 244.4 | 120 | 198.4 | 118.4 | 161.6 | 113.6 | 123.2 | 111.6 | 93.6 | 107.6 | |||||||||
| LXPL-RFCF-50L | SLD190 -50 (50HP) |
1 | 35 | 94.5 | 32 | 78.6 | 30.7 | 64.6 | 29.7 | 53.2 | 28.9 | 41.6 | 28.3 | 150 | Ф28 | Ф76 | Ф57 | Ф45 | 2200×1500×1700 |
| 40 | 90.1 | 38.7 | 74.6 | 36.7 | 59.5 | 34.6 | 47.8 | 33.6 | 37 | 32.3 | |||||||||
| 45 | 85.9 | 42.2 | 69.8 | 41.6 | 56.9 | 39.9 | 43.3 | 39.2 | 32.9 | 37.8 | |||||||||
| LXPL-BRFCF2 -100L |
2 | 35 | 189 | 64 | 157.2 | 61.4 | 1292 | 59.4 | 104.6 | 57.8 | 83.2 | 56.6 | 200 | Ф35 | Ф89 | Ф76 | Ф57 | 2400×1650×1700 | |
| 40 | 180.2 | 77.4 | 149.2 | 73.4 | 119 | 692 | 95.6 | 67.2 | 74 | 64.6 | |||||||||
| 45 | 171.8 | 84.4 | 139.6 | 83.2 | 113.8 | 798 | 86.6 | 78.4 | 65.8 | 756 | |||||||||
| LXPL-BRFCF3 -150L |
3 | 35 | 283.5 | 96 | 235.8 | 92.1 | 193.8 | 89.1 | 156.9 | 86.7 | 124.8 | 84.9 | 250 | Ф45 | Ф108 | Ф76 | Ф57 | 3000×1800×1700 | |
| 40 | 270.3 | 116.1 | 223.8 | 110.1 | 178.5 | 103.8 | 143.4 | 100.8 | 111 | 96.9 | |||||||||
| 45 | 257.7 | 126.6 | 209.4 | 124.8 | 170.7 | 119.7 | 129.9 | 117.6 | 98.7 | 113.4 | |||||||||
| LXPL-BRFCF4 -200L |
4 | 35 | 378 | 128 | 314.4 | 122.8 | 258.4 | 118.8 | 209.2 | 115.6 | 166.4 | 113.2 | 300 | Ф57 | Ф108 | Ф89 | Ф76 | 4500×2000×1800 | |
| 40 | 360.4 | 154.8 | 298.4 | 146.8 | 238 | 138.4 | 191.2 | 134.4 | 148 | 129.2 | |||||||||
| 45 | 343.6 | 166.8 | 279.2 | 166.4 | 227.6 | 159.6 | 173.2 | 156.8 | 131.6 | 151.2 | |||||||||